RCD
The Residual Current Device, or RCD, is an essential guardian in the world of electrical safety. With steadfast dedication, it ensures the protection of both residential and commercial spaces, vigilantly shielding them from the hidden dangers of electrical faults. Its presence fosters a safe and secure environment, bringing peace of mind to every corner.
At the heart of its operation, the RCD serves as a reliable defense against electric shocks, providing a comprehensive safeguard against potential hazards and even life-threatening situations. It achieves this by continuously monitoring the equilibrium of electrical currents within specific circuits. The moment it detects any disparity that signals a diversion of electrical flow, this alert device swiftly disrupts the circuit, acting immediately to prevent any harm.
This phenomenon, known as 'earth leakage' or 'Residual Current,' can arise from various circumstances such as faulty wiring or accidents during DIY projects. Imagine accidentally striking a cable while hanging a picture frame or mistakenly cutting through a wire with a lawnmower. In these cases, the errant electricity seeks the easiest path, which might unfortunately be through the person handling the tool, closing the circuit and risking electric shock.
Product category | CIRCUIT BREAKER | ||
Product type | RESIDUAL CURRENT OPERATED CIRCUIT-BREAKERS | ||
Product model | TML1-100 | ||
Business information | MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo:pad printing, laser printing (customized design are acceptable) |
||
Technical data | Standard | IEC61008-1, GB16916-1 | |
Electrical features | Rated curret (In) | 25A, 40A, 63A | |
Model | Electromagnetic | ||
Type | AC, A, S, G | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated conditional short-circuit current Inc) | 10KA | ||
Rated residual making and breaking capacity(IΔm) | 1000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 10,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |