RCD
The Residual Current Device, often cherished as the RCD, is a paramount defender in the domain of electrical safety, tirelessly safeguarding both residential and commercial settings. It is an indispensable line of defense against the potentially perilous threats posed by electrical hazards, assuring a protected and secure environment for everyone involved.
At its core, the RCD functions as an unwavering guardian against electrical shock, providing a vital layer of protection from possible injuries and even life-threatening incidents. It executes this essential role by meticulously monitoring the balance of electrical currents as they traverse designated circuits. Upon the slightest detection of an imbalance-an indication that the current might have deviated-this vigilant device springs into action instantly, severing the circuit in a split second to avert danger.
This phenomenon, known as 'earth leakage' or 'Residual Current,' can arise from a myriad of causes, such as subpar wiring quality or unintended accidents during DIY tasks. Envision the scenario when you inadvertently drill into a cable while hanging a picture frame or mistakenly cut through a wire with a lawnmower. In such situations, the errant electricity searches for the path of least resistance, which, regrettably, could be through the individual using the tool, thus completing the circuit and potentially resulting in an electric shock.
Product category | CIRCUIT BREAKER | ||
Product type | RESIDUAL CURRENT OPERATED CIRCUIT-BREAKERS | ||
Product model | TML1-100 | ||
Business information | MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo:pad printing, laser printing (customized design are acceptable) |
||
Technical data | Standard | IEC61008-1, GB16916-1 | |
Electrical features | Rated curret (In) | 25A, 40A, 63A | |
Model | Electromagnetic | ||
Type | AC, A, S, G | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated conditional short-circuit current Inc) | 10KA | ||
Rated residual making and breaking capacity(IΔm) | 1000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 10,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |