RCD
The Residual Current Device (RCD) is an indispensable guardian in electrical safety, offering paramount protection in both residential and commercial settings. Its role is pivotal in safeguarding lives and properties from the hazards of electrical shock.
An RCD acts as a vigilant sentinel, defending against potential injuries or fatalities stemming from electric shock. By meticulously monitoring the flow of electricity, it detects any discrepancy between the outgoing and incoming current across a network of circuits. This ingenious device operates on a straightforward yet effective principle: if the current entering the system does not match the current leaving, an anomaly is present, indicating that electricity is escaping elsewhere.
This electrical anomaly, often termed 'earth leakage' or referenced as 'Residual Current' in the RCD's designation, can arise from several issues such as faulty wiring or inadvertent mishaps during DIY tasks. Consider scenarios like accidentally drilling into a cable while mounting a picture hook or slicing through a cable with a lawnmower. In such instances, the errant electricity seeks the path of least resistance, potentially coursing through the appliance into the person operating it, thus forming a hazardous circuit and risking an electric shock.
Product category | CIRCUIT BREAKER | ||
Product type | RESIDUAL CURRENT OPERATED CIRCUIT-BREAKERS | ||
Product model | TML1-100 | ||
Business information | MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo:pad printing, laser printing (customized design are acceptable) |
||
Technical data | Standard | IEC61008-1, GB16916-1 | |
Electrical features | Rated curret (In) | 25A, 40A, 63A | |
Model | Electromagnetic | ||
Type | AC, A, S, G | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated conditional short-circuit current Inc) | 10KA | ||
Rated residual making and breaking capacity(IΔm) | 1000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 10,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |