Behold the groundbreaking RCBO from Taimu Electrical (Hangzhou) Co., Ltd., a cutting-edge Residual-current Circuit Breaker with integrated Overcurrent protection that transforms safety into an art form. Known in the industry circles as a GFCI or Ground Fault Circuit Interrupter, this sophisticated device is meticulously engineered to comply with the prestigious standards of IEC/BS EN 61009-1 and GB16917. The RCBO brilliantly combines the robust capabilities of both an MCB and an RCD (RCCB), delivering formidable protection against overloads, short-circuits, and deviations in residual current with exceptional precision. The revered Timelec RCBO stands as a vigilant guardian for your electrical systems, ensuring unmatched safety and reliability by expertly managing these critical operations. Designed for unparalleled performance, it is available in two distinctive types based on its tripping mechanism: the ELE (Electronic) and ELM (Electromagnetic) models. Moreover, it presents four core types crafted to cater to the diverse waveform and frequency demands of fault currents: Type Ac, Type A, Type F, and Type B. These carefully curated options are backed by national standards across numerous countries, emphasizing its global versatility and steadfast dedication to safety.
Product category | CIRCUIT BREAKER | ||
Product type | Residual current operated circuit-breakers with integral overcurrent protection (RCBO) | ||
Product model | TMRO10-63 | ||
Product photo | ![]() |
||
Business information |
MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo: pad printing, laser printing (customized design are acceptable) |
||
Unique selling proposition | Prevention from overloading and short-circuit currents, Detection of the earth leakage current. Protection against indirect contacts and direct contacts. Preventing fire hazard in cause of circuit fault. Widly used in residual building and other recombiner distribution boxes |
||
Technical data | Standard | IEC 61009-1, GB16917.1 | |
Electrical features | Rated current (In) | 6A, 10A, 16A, 20A,25A, 32A, 40A, 50A, 63A | |
Trip curve | B, C, D | ||
Model | Electronic/Electromagnetic | ||
RCD Type | AC, A | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240V/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Energy limiting class | 3 | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated breaking capacity (Icn) | 6KA/10KA | ||
Rated operating short circuit breaking capacity (Ics) | 6KA/7.5KA | ||
Rated residual making and breaking capacity(IΔm) | 3000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Surge current resistance / at (8/20) μs | 3KA | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 20,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |