RCD
The Residual Current Device, fondly known as RCD, is an essential guardian in the realm of electrical safety, safeguarding both residential homes and bustling commercial environments. Its vital role cannot be overstated, as it stands as a robust protector against potential electrical hazards.
At the heart of its operation, the RCD stands vigilant as a defender against the peril of electric shocks, offering a protective shield that can prevent injuries and even save lives. It meticulously monitors the equilibrium of electrical current as it courses in and out of designated circuits. Should it detect any imbalance, a telltale sign that some current has veered off course, the RCD springs into action, promptly severing the circuit to prevent harm.
Such situations, termed 'earth leakage' or 'Residual Current,' may emerge from an array of issues such as inferior wiring or unexpected accidents during DIY endeavors-picture drilling into a hidden cable while hanging a cherished picture or accidentally nicking a wire with a lawnmower blade. In these moments, the wandering electricity seeks out the easiest path, which could devastatingly be through the individual handling the tool, thereby completing the circuit and triggering a potentially dangerous electric shock.
Product category | CIRCUIT BREAKER | ||
Product type | RESIDUAL CURRENT OPERATED CIRCUIT-BREAKERS | ||
Product model | TML1-100 | ||
Business information | MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo:pad printing, laser printing (customized design are acceptable) |
||
Technical data | Standard | IEC61008-1, GB16916-1 | |
Electrical features | Rated curret (In) | 25A, 40A, 63A | |
Model | Electromagnetic | ||
Type | AC, A, S, G | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated conditional short-circuit current Inc) | 10KA | ||
Rated residual making and breaking capacity(IΔm) | 1000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 10,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |