Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the groundbreaking RCBO from Taimu Electrical (Hangzhou) Co., Ltd., a cutting-edge Residual-current Circuit Breaker with Overcurrent protection. Revered in the industry as either a GFCI or Ground Fault Circuit Interrupter, this sophisticated device is meticulously engineered to comply with the elite standards set forth by IEC/BS EN 61009-1 and GB16917. The RCBO masterfully combines the robust functionalities of both an MCB and an RCD (RCCB), delivering exceptional protection against overload, short-circuit, and residual current anomalies. The distinguished Timelec RCBO stands as a vigilant guardian for your electrical systems, ensuring unmatched safety and reliability by adeptly managing these critical operations. Expertly designed for peak performance, it is available in two distinct types based on its tripping mechanism: the ELE (Electronic) and ELM (Electromagnetic) variants. Additionally, it provides four primary types expertly crafted to address diverse waveform and frequency demands of fault currents: Type Ac, Type A, Type F, and Type B. These carefully curated options are endorsed by national standards worldwide, demonstrating its global adaptability and steadfast commitment to safety.
Product category | CIRCUIT BREAKER | ||
Product type | Residual current operated circuit-breakers with integral overcurrent protection (RCBO) | ||
Product model | TMRO10-63 | ||
Product photo | ![]() |
||
Business information |
MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo: pad printing, laser printing (customized design are acceptable) |
||
Unique selling proposition | Prevention from overloading and short-circuit currents, Detection of the earth leakage current. Protection against indirect contacts and direct contacts. Preventing fire hazard in cause of circuit fault. Widly used in residual building and other recombiner distribution boxes |
||
Technical data | Standard | IEC 61009-1, GB16917.1 | |
Electrical features | Rated current (In) | 6A, 10A, 16A, 20A,25A, 32A, 40A, 50A, 63A | |
Trip curve | B, C, D | ||
Model | Electronic/Electromagnetic | ||
RCD Type | AC, A | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240V/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Energy limiting class | 3 | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated breaking capacity (Icn) | 6KA/10KA | ||
Rated operating short circuit breaking capacity (Ics) | 6KA/7.5KA | ||
Rated residual making and breaking capacity(IΔm) | 3000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Surge current resistance / at (8/20) μs | 3KA | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 20,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |