RCD
The Residual Current Device, or RCD, is an indispensable guardian in the realm of electrical safety, tirelessly vigilant in its mission to protect both residential and commercial spaces. It serves as a crucial barrier against the hidden dangers of electrical faults, ensuring an environment of tranquility and security.
At its core, the RCD acts as a steadfast defender against electric shock, providing essential protection against potential hazards and life-endangering situations. It achieves this by expertly monitoring the equilibrium of electrical current across specified circuits. Upon identifying any imbalance, indicating a deviation in current, this vigilant device swiftly halts the circuit, acting immediately to prevent danger.
This phenomenon, termed 'earth leakage' or 'Residual Current,' can arise from various situations, such as substandard wiring or accidents during DIY projects. Picture yourself accidentally piercing a cable while hanging a picture or unknowingly cutting a wire with a lawnmower. In these scenarios, the errant electricity seeks the path of least resistance, potentially through the individual handling the tool, completing a circuit and resulting in an electric shock.
Product category | CIRCUIT BREAKER | ||
Product type | RESIDUAL CURRENT OPERATED CIRCUIT-BREAKERS | ||
Product model | TML1-100 | ||
Business information | MOQ: 120pcs Payment: T/T, L/C Delivery time: 15-60 days Loading Port: Ningbo or Shanghai, China Certification: ISO9001:2015 Logo:pad printing, laser printing (customized design are acceptable) |
||
Technical data | Standard | IEC61008-1, GB16916-1 | |
Electrical features | Rated curret (In) | 25A, 40A, 63A | |
Model | Electromagnetic | ||
Type | AC, A, S, G | ||
Pole | 2P, 4P | ||
Rate voltage (Ue) | 240/415V | ||
Insulation voltage(Ui) | 500V | ||
Rated frequency | 50/60Hz | ||
Rated residual operating current (IΔn) | 30mA, 100mA, 300mA | ||
Rated conditional short-circuit current Inc) | 10KA | ||
Rated residual making and breaking capacity(IΔm) | 1000A | ||
Rated impulse withstand voltage (Uimp) | 4KV | ||
Electrical life | 4,000 | ||
Pollution degree | 2 | ||
Mechanical features | Mechanical life | 10,000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily averages35°C) | -25°C +40°C | ||
Storage temperature | -25°C +70°C | ||
Installation | Terminal connection type | Cable, busbar | |
Connection capacity (input) | 25mm2 | ||
Connection capacity (output) | 25mm2 | ||
Tightening torque (input) | 2.5Nm | ||
Tightening torque (output) | 2.5Nm | ||
35mm DIN rail |